11-2 A steady-flow Carnot refrigeration cycle uses refrigerant-134a as the working fluid. The refrigerant changes from saturated vapor to saturated liquid at 30°C in the condenser as it rejects heat. The evaporator pressure is 160 kPa. Show the cycle on a T-s diagram relative to saturation lines, and determine
a) the coefficient of performance,
b) the amount of heat absorbed from the refrigerated space, and
c) the net work input. Answers:
a) 5.64,
b) 147 kJ/kg,
c) 26.1 kJ/kg
 
 